A CAN network on a rotary table may communicate normally during commissioning, then produce intermittent errors when the table starts indexing or a nearby drive switches. Replacing the slip ring immediately may restore communication temporarily, leave the fault unchanged, or introduce a different wiring problem. The useful first question is not whether CAN can pass through a slip ring. It is whether the installed rotary interface is disrupting the electrical bus, the supply to a rotating node, or the timing of the machine's control messages.
A contact-based CAN bus slip ring carries the conductors across a moving boundary. It does not normally process CAN messages, acknowledge frames, retransmit data or recover a controller from bus-off. Those functions belong to the network electronics. Diagnosis must therefore relate the behavior of those electronics to the conditions at the rotary connection.
This guide focuses on high-speed Classical CAN in industrial machinery. Use approved diagnostic points, guarded motion and the equipment manufacturer's isolation procedure; safety-network changes and live collector disassembly are outside its scope.
First identify which part of the machine has stopped communicating
Consider an indexing table with a controller in the stationary cabinet and a sensor module on the rotating fixture. The CAN trunk passes through the rotary interface, and the same assembly may transfer DC power to the sensor module. If the controller reports a missing sensor message, at least three different events could have occurred:
- The message was sent, but transmission was disrupted by the communication path.
- The rotating module stopped sending because its local supply dropped or its controller reset.
- The message was delivered too late for the machine's configured timeout, although the CAN network continued to communicate.
A stopped-ring resistance check cannot distinguish those failures. The useful record combines the controller's transmission status, an independent bus trace, the rotating node's supply or reset status and the application's received-update history.
Start by drawing the installed system, from the stationary controller through its cable, connector, rotating contacts and rotating-side harness to the last CAN node. Mark all branches, both physical bus ends, the two terminations if the system uses conventional high-speed CAN, the transceiver supply, local reference, shield connections and protective earth. Show where the rotating electronics receive power. If a gateway is present, distinguish its two networks instead of treating them as one passive copper path.
A multi-lead rotary assembly may contain conductors of several colors and sizes. Neither color nor conductor thickness identifies CAN_H, CAN_L, the signal reference or power return. Obtain the circuit schedule and connector pinout for the installed assembly before making comparisons. For an assembly that also carries drive power, the adjacent switching circuits belong on this drawing. They are possible aggressors even when the CAN pair itself has no visible damage. ByTune's power and data slip ring guide addresses mixed-circuit architecture; the following sections focus on the CAN-specific fault evidence.

What a normal termination reading can and cannot establish
For a conventional high-speed CAN linear trunk, two nominal 120-ohm resistors terminate the physical ends. The slip ring's location does not determine where termination belongs. A ring between two sections of the same trunk is not an additional bus end.
With the machine electrically isolated and the network in the measurement condition specified by its manufacturer, the two terminators in parallel normally give approximately 60 ohms across CAN_H and CAN_L. This is the principle described in maxon's CAN wiring guidance. Confirm the actual circuit arrangement and switchable internal terminators before interpreting the reading.
| Reading or observation | What it can suggest | What to verify next |
|---|---|---|
| Approximately 60 ohms | Both nominal terminators may be electrically visible | Confirm that they are at the actual ends, not both on one side of the rotary interface |
| Approximately 120 ohms | One terminator may be missing or disconnected from the measurement point | Inspect topology, connector pinout and the intended continuity of the remote section |
| Approximately 40 ohms | Three nominal 120-ohm terminators may be connected in parallel | Check built-in controller, sensor and analyzer termination settings |
| Reading changes at different approved stationary angular positions | An intermittent conductor, connector or contact may alter the measured circuit | Localize the path using isolated sections and the approved measurement boundary |
The values are ideal resistor-network examples, not slip-ring resistance limits. Transceiver circuitry, other components and alternative termination arrangements can affect the measurement. A correct reading is only a preliminary topology check. It does not show whether an installed pair has adequate timing margin, whether a contact briefly opens during motion, or whether both termination resistors are correctly located.
Avoid putting an extra termination resistor at a rotary connector merely because the connector looks like the end of a cable. It can change bus loading without solving the original fault.
Read the CAN error type and controller state first
A controller that reports a bus error is not necessarily identifying the component that caused it. Read the error type, the reporting node and the state transition before deciding whether to investigate the rotary contacts. Analog Devices' CAN implementation guide explains the underlying protocol checks.
| Reported error | What the controller detected | Most useful CAN-specific comparison |
|---|---|---|
| ACK error | A transmitting node did not see a valid acknowledgment | Check whether a powered receiver on the far side is participating at the correct bit rate; confirm the monitor is not listen-only |
| Bit error | A transmitted state did not match the monitored bus state where such a mismatch is an error | Examine the differential trace, transmitter behavior and another node's event log; normal arbitration is not a bit error |
| Stuff error | The received sequence violated the stuffing rule in a stuffed field | Compare timing, pulse shape, and repeated short disturbances across the rotary channel |
| CRC error | The receiver's integrity check failed | Compare receiving-node errors with the original transmission and local reference/supply conditions |
| Form error | A fixed-format portion of the received frame had an invalid state | Compare the affected frame region and timing, then inspect reflections or transient interference |
None of these labels, in isolation, proves contact wear. A CRC error can be the result of a disturbance originating outside the slip ring; an ACK error can result from an unpowered or incorrectly configured receiver. Normal arbitration, during which a competing transmitter defers to a higher-priority message, is not itself a communication fault.
A Classical CAN controller uses a transmit error counter (TEC) and a receive error counter (REC) to manage fault confinement. Error-passive operation is reached when either counter exceeds 127; bus-off is reached when TEC exceeds 255. Read the actual controller's documentation for how these states and counter values are exposed, particularly where the hardware does not report a literal count of 256. Error-passive nodes can still participate in communication; a bus-off node cannot participate normally until it recovers under its controller and machine configuration. Microchip's controller error-handling documentation describes the counter-dependent states. Do not treat a rising REC alone as the bus-off threshold.
Counters are state variables, not cumulative error totals. Successful communication can reduce them, so a final healthy value does not establish an error-free run. Preserve the first observed error, last error code if available, counter history and state transitions. A bus-off event is a consequence requiring diagnosis, not an instruction to repeatedly reset the controller. The equipment's approved recovery behavior must remain intact.
A valid ACK is not proof that the intended rotating device received the command
CAN acknowledgment is supplied by a participating receiver that has correctly received the frame at the protocol level; it does not establish that the intended application accepted or acted on the data. If a stationary controller and another stationary node share the trunk, the second stationary node can acknowledge a frame even when the rotating-side section has become disconnected. In that situation the sender may report success while the rotating device never receives the command.
Conversely, a bench test consisting of a transmitter and a silent monitoring adapter can produce ACK errors even with an intact signal path. Document the monitor mode and termination before comparing it with the installed network. Where the intended rotating receiver can report message reception, compare its own event or application log with the sender's transmission status. Never remove a functioning machine node or alter termination merely to force an ACK test; use a separately approved reference fixture when that isolation is needed.
Separate three CAN failure paths using synchronized records
The general slip ring electrical noise diagnostic guide already describes how to compare rotation and adjacent switching. For CAN, the purpose of repeating an approved operating condition is more specific: identify whether the transmitted frame was corrupted, the receiving device stopped participating, or the application deadline was missed despite valid traffic.
| Evidence stream | What to record | Why it changes the decision |
|---|---|---|
| Sender controller | Message generation or transmit request, transmit completion status, TEC, state transitions | Distinguishes an unsent or unsuccessfully transmitted update from a completed transmission |
| CAN monitor | Valid frame timestamps, identifiers, error indications, capture-loss status | Shows traffic visible at that point on the bus; does not by itself prove delivery to the intended receiver |
| Rotating node | Local supply status, receive/application counter, documented reset or state indicators | Separates a broken data path from loss of participation or an application reset |
| Machine controller | Expected update times, accepted updates, timeout or freshness flag | Defines whether the machine requirement was actually met |
| Motion reference | Shaft angle or cycle marker, speed, direction and actual load-switching events | Places electrical and application events in their mechanical context |
Use a common trigger or a characterized timestamp relationship between instruments. If a supply logger and CAN logger have independent clocks, establish their alignment and maximum timing uncertainty before stating that one event preceded another. At high traffic, verify whether the logger is capable of capturing error indications and whether the capture software reports dropped records. A trace with unknown capture loss is insufficient for a zero-error acceptance claim.
For example, if the sender reports successful transmission while the rotating receiver logs no new update and another stationary node is acknowledging frames, investigate the path to the intended receiver rather than accepting the sender's ACK as evidence of end-to-end operation. If the rotating device records a reset before its expected messages disappear, inspect the supply and return path first. If both endpoints log valid frames but the control system declares the data stale, inspect scheduling, message filtering and application timestamps before changing the slip ring.
In a guarded fixture, a reference run with a fixed harness and a run through the rotary interface may help establish the difference attributable to the interface. Keep the controller timing, termination, traffic and electrical configuration comparable; document any unavoidable cable-length or connector changes. Do not route a temporary bypass cable across moving machinery.
Compare CAN failures by angular exposure and message opportunity
Raw error counts can mislead when an indexing machine spends most of its cycle at a particular angle. A useful comparison assigns each observed event to the relevant shaft sector and records both its dwell time and the number of expected updates for the monitored message. Keep an error-frame tally separate from a missing-update tally; they measure different things.
| Signature in the synchronized log | Discriminating check |
|---|---|
| ACK errors rise near a repeatable angle, and the far-side node remains powered | Check whether the far-side node can receive and acknowledge frames; inspect the approved connector and rotary path boundary |
| Stuff or bit errors coincide with a switching event, even without movement | Compare the differential and common-mode signals at the node; investigate the switching path before attributing the fault to wear |
| A particular message arrives late but other traffic remains valid | Compare its configured period, arbitration priority, queueing and application freshness rules |
| A rotating node disappears, then sends startup traffic | Compare the documented reset indicator with local supply and reference records |
| Both sides report error flags | Correlate the earliest reliably time-aligned observation; a shared-bus error flag can be seen beyond its point of origin |
For periodic traffic, determine whether the selected rate and shaft speed exercise the full angular range. Fixed message timing can repeatedly sample a limited set of angles when the electrical and mechanical cycles are synchronized. Repeat at other permitted speeds or with a separate representative test traffic pattern, then verify the actual production timing unchanged. If a sector has little or no communication exposure, report the gap rather than calling it fault-free.
A symptom that repeats at a fixed angle supports further investigation but is not proof of an internal track defect. A cable, connector or machine action can repeat at the same position. The general mechanical and noise-isolation procedure remains in the linked noise-diagnosis guide; here the evidence is the CAN error and application record.
When contact variation is actually the limiting mechanism
Sliding contacts can introduce short high-resistance events or momentary interruption, while the internal electrical geometry can introduce impedance discontinuities. These are different ways a rotary connection can disturb a CAN waveform. The CAN Newsletter article by Moog engineers on CAN transmission through slip rings discusses both effects and the role of contact design and the operating environment.
Contact-related disruption may be extremely brief relative to the response of a handheld resistance meter. An average resistance value therefore cannot establish the absence of transient events. Conversely, an impedance-related waveform defect may appear when the contacts are electrically continuous. Selecting a contact material by itself is not a complete data-channel design.
When the evidence points toward the rotary section, compare accessible measurements before and after that section using equivalent probe arrangements and synchronized timing where feasible. Include rotor and stator connectors in the initial boundary, then narrow the boundary only when approved access allows it. The observation that an error is present on both sides of a shared bus does not by itself locate its origin: error signaling can propagate through the network.
At approved test points, examine the differential signal (CAN_H minus CAN_L) and, where the instrument and circuit permit, the common-mode level (the mean of the two line voltages relative to the specified local reference). A common-mode shift can stress the receiver even when the differential trace appears plausible. Compare the actual transceiver's specified input range and bit timing with the measured waveform rather than imposing a universal voltage mask. Use suitable probes and test connections that do not add significant stubs or compromise isolation. Trigger on the reported frame error or time-correlate the waveform with the controller log; an ordinary averaged resistance reading cannot reveal which portion of the frame was affected. If waveform access is not available, retain the uncertainty in the diagnosis.
If the reference network passes and the rotating test repeatedly fails, the rotary installation deserves deeper examination. It remains necessary to distinguish internal contacts from external leads, connector transitions and mechanical mounting. Consult the manufacturer before opening, cleaning or adjusting an assembly; those actions may change the contact system and invalidate the comparison.
Distinguish a communication path problem from a rotating power problem
Many small CAN devices receive power through other conductors in the same slip ring. A supply interruption at a rotating sensor can present as an intermittent CAN fault even when the pair is intact. Power return resistance, shared return paths, local connector damage and switching transients may all affect the device's supply or reference.
Look for a repeatable sequence: supply disturbance, device reset indication, absence of expected messages, then initialization traffic or recovery. Compare that sequence with error frames reported by the stationary and rotating electronics. Use the device's documented reset indicators or diagnostic messages rather than guessing that a gap is a reboot.
A power problem and a CAN physical-layer problem can coexist. For example, a disturbance on a shared reference may affect a transceiver without fully resetting its host. Check the specified common-mode operating range of the actual transceiver, and distinguish the signal reference from protective bonding and shield continuity. Do not disconnect protective earth or change the shield scheme experimentally on a live machine.
If a correctly specified rotating supply remains within its validated limits while communication errors follow the rotary interface, continue investigating the data path. If the node supply violates its documented operating limits first, correct that condition and repeat the network test before ordering a new signal slip ring.
Recheck the interface after a CAN electronics upgrade
Classical CAN and CAN FD have different timing requirements. CANopen is a higher-layer protocol rather than a guarantee of a particular rotary channel construction. A slip ring qualified with one set of transceivers and bit timing should not automatically be accepted after changing the network.
The CAN in Automation announcement of May 21, 2026 concerning a high-bit-rate mode for CAN FD Light illustrates why the network variant matters: it describes a specific commander/responder implementation, not an extension of a Classical CAN slip ring rating. The relevant action for an OEM is to specify the exact interface and validate the finished rotary path at the new timing, traffic and electrical duty. Do not infer CAN FD Light, CAN FD or any specific speed rating from the word CAN on a product-family page.
When updating an installed machine, retain a trace from the previous working configuration and record the new transceiver, nominal bit rate, data-phase settings where applicable, firmware, message schedule and physical wiring. This prevents a controller or software change from being mistaken for an age-related contact failure.
Build an acceptance record that detects hidden retries and missed updates
A dynamic acceptance test should establish whether the complete interface meets the machine's communication requirements, not merely whether an analyzer can decode a frame. Agree the requirements with the system owner before testing; the permissible event rate, deadline and recovery behavior depend on the application.
| Record field | Required interpretation |
|---|---|
| Configuration | Device and firmware versions, bus implementation, bit rate, timing, topology, cable and terminations |
| Mechanical exposure | Test duration, rotations, direction, angular coverage, indexing and dwell conditions |
| Electrical exposure | Adjacent circuit loading, switching states and supply observations |
| Network events | Error events visible to the logger, controller state changes, retry indicators if available, bus-off occurrences |
| Application delivery | Expected and received updates, sequence discontinuities where available, longest update gap, deadline violations |
| Measurement quality | Logger timebase, synchronization, filter settings, capture loss and unavailable diagnostics |
| Acceptance | Agreed limits, actual observations, exceptions and responsible reviewer |
Measure application delivery using the existing message sequence or an agreed test payload when available. On a periodic-message network, expected-message windows can be compared with timestamped arrivals, accounting for the permitted schedule variation. A CAN identifier alone does not necessarily identify a unique application update. When high-priority traffic delays a lower-priority message, the application can miss a deadline even without a physical-layer error. Compare the trace against the configured message schedule and priorities before classifying a late update as a rotary contact fault. An analyzer may also omit error frames or lose records under high traffic; verify capture capability before interpreting a clean log.
Report an observed failure count with its exposure. A test with zero recorded events covers only the duration, traffic and motion actually exercised. It is not proof of zero lifetime failures. Do not label a ratio of error events to valid logged frames as a measured bit-error rate: retransmissions, invisible errors and the number of transmitted bits are different quantities.
Judge the message deadline separately from the bus error limit
For a recurring control message, define the expected production period and the maximum permissible age or inter-arrival gap using the machine's actual specification. Compute the maximum gap between accepted, fresh updates at the intended receiving application, not just successive frames with the same identifier on a monitor. A retry may deliver a correct frame after the allowed deadline. A duplicate payload may not be a fresh update. Where the application provides a sequence number, use its documented wraparound and reset behavior when identifying missing updates. If the software cannot report freshness, the test record should say so rather than substituting a bus-level ACK for the unavailable application evidence.
The acceptance report should therefore record separate results for controller fault-confinement events, captured bus errors and application deadline compliance. A measurement without the relevant exposure or capture-quality information remains inconclusive. The responsible machine engineer defines permissible event counts and deadlines; a supplier's standalone continuity test does not establish these limits.
For maintenance investigations, preserve the original trace before changes. After the corrective action, repeat the relevant failure-producing condition and then the complete intended operating profile. This makes a repair result comparable rather than merely anecdotal.
When to request a different slip ring configuration
The diagnostic record should support one of three outcomes: correct a fault outside the rotary assembly; repair or replace a defective rotary assembly under the supplier's instructions; or review the architecture because the existing assembly was never specified for the required CAN channel and combined duty.
A proposed replacement requires more than two signal leads. ByTune's through-bore products illustrate why the mechanical envelope, connector shell and circuit assignment must all be checked independently. A matching connector shape does not prove matching pinout, and an identifiable product label does not establish CAN qualification. Submit the network drawing, CAN implementation and rates, actual transceiver or controller types, cable and connector definitions, grounding and shielding arrangement, power circuits and switching conditions, mechanical envelope, rotation profile, operating environment and agreed acceptance criteria. Attach the fault log if replacing an existing interface.
ByTune lists CAN among its custom slip ring signal options and includes CAN-BUS among the signal options on its capsule slip ring category page. A through-hole slip ring may be a mechanical alternative when a shaft or other service must pass through the center; its CAN channel must be specified separately. These are useful starting points when comparing installation geometry. The electrical configuration and test conditions must be agreed for the actual ordered assembly rather than inferred from the product family or total circuit count.
The most useful request is not simply a CAN-compatible slip ring. It is a clearly defined communication path and a measurable operating requirement. A supplier can then evaluate the intended configuration against the mechanical envelope and electrical conditions, while the machine owner retains a meaningful acceptance test for the installed system.